AnalogManager
Operation (Type)
Bitmap
Function (Output)
Divide
Analog Result = (A1 / A2) * C1
Boolean Result goes TRUE, if Analog Result > 0
Switch
Analog Result = A1, if L1 = TRUE
Analog Result = A2, if L1 = FALSE AND L2 = TRUE
Analog Result = C1, if L1 = FALSE AND L2 = FALSE
Boolean Result goes TRUE, if Analog Result > 0
Notes
Icon shows switch positions L1/L2 as FALSE.
Common use could be to switch between A1 and A2: Set L2
= TRUE; use L1 to switch.
Maximum
Analog Result = MAX(A1 , A2)
Boolean Result goes TRUE, if A1 > A2
Minimum
Analog Result = MIN(A1, A2)
Boolean Result goes TRUE, if A1 < A2
In Band
Analog Result = ABS(A1 - A2)
Boolean Result goes TRUE, if (ABS(A1 - A2) <= C1)
C1 = maximum tolerance for being "in band"
660
easYgen-3000XT Series
B37574
4 Configuration
4.9.1 Operations
Released