Rev.
Date
Editor
Changes
• Modbus Master uses always the port number 501 instead of the configured one.
•
This is fixed now.
K
2020-09
TM
NEW Software Revision Release 2.10-1 or higher
NEW features & functions
• The AnalogManager variables "Free analog values" 24.05 to 24.08 are write-
•
protected with code level CL1.
╚═▷ “9.4.2.15 Group 24: Free analog values”
• In operation mode MANUAL the discrete raise/lower function is now available with
•
configurable ramp rates.
╚═▷ “4.4.4.7 Discrete Raise/Low Function”
• Expansion of the "Mains Voltage increase" monitor on up to 6 phases.
•
• To reach the component certification VDE-AR-N 4105 the password code level of
•
some mains decoupling parameter are changed:
◦ Mains voltage increase limit ID8807 from code level CL2 to CL1
◦
◦ Mains undervoltage 1 delay time ID3005 from code level CL2 to CL1
◦
◦ Mains undervoltage 2 delay time ID3011 from code level CL2 to CL1
◦
• The CANopen-Interface-3 error flag was missing in the modbus protocol 5016 and
•
is now available.
╚═▷ “The following data protocols are implemented to be used”
• Introduction of a Ethernet Address Network Check.
╚═▷ “4.7.5 Ethernet Interfaces”
•
• Expansion of the J1939 ECU handling. Introduction of a new sequencer file
•
"Volvo_EMS_1.3_49058".
╚═▷ “4.7.4.2.2 J1939 Interface”
Corrections/Repairs
• The Parameter ID511 "Remote reactive power setpoint" is getting the format
•
(Signed INT32). This allows now to send negative kvar setpoints to the easYgen.
• Start counter: Counter is now working too if changed from STOP to AUTO or TEST
•
during Start req. in AUTO is already true and if there is no preglow.
• The generator excitation limiter function and indication is disabled if reactive
•
control in the device is disabled.
• In cases the easYgen runs the genset with breaker transition mode "Open
•
transition": It could lead under special circumstances that the mains settling time
is shortened to 2 seconds even there is no need for. This is fixed now.
• In cases the operation mode is configured in order not to go automatically into
•
STOP due to a shutdown alarm and a MCB closure failure shall cause an
emergency run: It could lead under special circumstances that the emergency run
state in the event logger is steadily retriggered. This is fixed now.
J
2020-04
TM
NEW Software Revision Release 2.10 or higher
NEW features & functions
• Introduction of a Modbus Master functionality.
•
• Introduction of a Photovoltaic (PV) inverter load reduction function including of a
•
monitor feature.
╚═▷ “4.4.4.5.6 Photovoltaic (PV) load reduction regulated mode”
• Separate parameters for mains over/under voltage and over/under frequency
•
hysteresis.
• Writing LDSS Reserve power into the device: The device allows now a remotely
•
frequently refreshed reserve power setting.
╚═▷ “Remote LDSS IOP reserve power ”
MOP
╚═▷ “Remote LDSS MOP reserve power ”
• Providing of a monitoring function for Ethernet issues.
•
• LDSS: The current reserve power setting (Parameter, LM Parameter or from RAM
•
variable) is indicated in the ToolKit Status "States easYgen / Sequencing" screen.
• The easYgen provides a "Reboot" parameter in ToolKit and HMI.
•
• Communication protocols 5014 and 5016 are updated with
•
27
easYgen-3000XT Series
B37574
1 General Information
1.1 Revision History