9.2.9
Additional Data Identifier
9.2.9.1
Receive Data (sent from remote control to the easYgen)
General notes
The device accepts receive data from outside. These data are usually remote control
data, with which the genset control starts and stops the operation or runs different
setpoints.
These data do not require a password level to be accepted. They are overtaken into a
non-volatile memory and are lost, if the device is powered down.
Ensure Security!
Transmitting data from outside of the remote control needs secure (network)
communication. Do not connect the easYgen with the internet as long the security
aspects are not considered! Consider an IP responsible person to discuss proper security
procedures like placing routers and fire walls.
Take care for sufficient protection of Ethernet communication.
Remote control word 1
Object 21F7h (Parameter 503)
This object is required for remote control. The data type is UNSIGNED16.
The internal parameter 503 of the easYgen must be set to react on the remote control
instructions. This is performed by sending rising signals for the respective bits (refer to
for the priority of start and stop signals).
Para‐
meter
no.
Object
ID
Name
Unit
Data
type
Note
503
21F7h
Control word 1
Bit field
unsigned16
Bit 15
Not used
Bit 14
Not used
Bit 13
Not used
Bit 12
Not used
Bit 11
Not used
Bit 10
Not used
Bit 9
Shutdown command
To shut down, a "0" must be
written and then a "1"
Bit 8
Not used
Bit 7
Not used
Bit 6
Not used
Bit 5
Not used
Bit 4
Ext. Acknowledge
(rising edge) Must be
To acknowledge, a 0 must be
written and then a 1
1064
easYgen-3000XT Series
B37574
9 Appendix
9.2.9 Additional Data Identifier
Released