Rev.
Date
Editor
Changes
◦ Negative energy counters
◦
◦ Active and reactive power setpoints
◦
◦ ISOCH information
◦
• Improved System Interconnectivity by providing advanced CANopen and Modbus
•
access on Analog- and LogicsManager variables.
• Redundant load share Ethernet A and CAN with alarm. indication is possible.
•
• The timer setting over the ToolKit screen is improved to make the configuration
•
more comfortable. There are some configuration examples added.
Corrections/Repairs
• Breaker transition mode "Closed Transition": Being in island mode with multiple
•
running easYgens did not allow constant power control in the single easYgens.
This is fixed now.
• Phase shift (ROCOF) - Not possible to trigger in Decoupling Test Mode. This is fixed
•
now.
• The disabling of the maintenance call by configure maintenance hours and days to
•
zero is improved. In the past one last maintenance call was executed even the
hours and days were RESET. This is fixed now.
• Improvement Modbus TCP slave handling: Changed receive of Modbus to fix
•
occasional blocking of TCP port in multiple Modbus setups.
H
2019-04
PC
NEW Software Revision Release 1.16 or higher
NEW features & functions
• The FRT mains monitoring is further expanded. (VDE-AR-N 4110). See
•
“4.5.1.3.2 Generator Overfrequency (Level 1 & 2) ANSI# 81O”
• The mains frequency measurement is optimized to reach faster and more reliable
•
response times regarding mains frequency monitoring. (VDE-AR-N 4110). See
“9.4.2.2 Group 02: Mains values”
• Some min. and max. adjusting values for configure mains decoupling monitorings
•
are changed to match the newest grid code demands. (VDE-AR-N 4110)
• Introduction of special mains limits to maintain the resynchronization of the
•
genset back to mains after a mains failure. (VDE-AR-N 4110). See
Reconnecting Mains Operating Range”
.
• Introduction of a generator reactive power setpoint [kvar] including the capability
•
to serve it through interface connection or any free analog input. See
“Remote reactive power setpoint”
.
• Introduction of different individually configurable reactive power setpoint filters
•
(PT1 characteristic). (VDE-AR-N 4110). See
╚═▷ “4.4.4.2.4 Reactive Power / Power
.
• Introduction of a Reactive power – Voltage curve Q(V). (VDE-AR-N 4110). See
•
“4.4.4.2.5.3 Reactive Power Q(V) limit”
.
• Introduction of a Reactive power – Active power curve Q(P). (VDE-AR-N 4110). See
•
╚═▷ “4.4.4.2.5.2 Reactive Power Q(P)”
.
• Introduction of a Reactive power – Voltage curve Q(V) including voltage limitation.
•
(VDE-AR-N 4110). See
╚═▷ “4.4.4.2.5 Reactive Power Characteristic”
.
• Introduction of a special mains frequency value based on a 200ms gliding average
•
value to match an accuracy of 50mHz and better. (VDE-AR-N 4110). See
“9.4.2.2 Group 02: Mains values”
• The over frequency -active power decrease function is expanded with under
•
frequency -active power increase function. (VDE-AR-N 4110). See
Active Power – Frequency Function P(f)”
• Providing a LogicsManager command variable in order to blocking ROCOF Monitor
•
during FRT-cases. (VDE-AR-N 4110). See
╚═▷ “9.3.2.7 Group 07: Mains related
.
• Providing of a configurable hysteresis for mains voltage and frequency monitoring
•
(VDE-AR-N 4110) in Rev. J changed again.
• Introduction of a pole-slip monitoring function in parallel to mains operation. (VDE-
•
AR-N 4110)
╚═▷ “4.5.1.6.3 Pole Slip Monitoring”