4.1.5.10 Synchroscope busbar/mains
Fig. 106:
Synchroscope screen (example)
The needle indicates the actual phase angle between busbar and generator or mains.
Please take care for compensation settings with parameters
compensation GCB« and
»Phase angle GCB«.
If phase angle compensation
is active the compensated values are taken for
synchroscope display (and synchronization)!
WARNING!
Ensure correct synchronization configuration to avoid generator destructive power!
The 12 o'clock position on the top means 0° and the 6 o'clock position on the bottom
means 180°.
The actual phase angle is indicated on the bottom of the screen. The maximum positive
and negative phase angles are indicated 'green'. The length of the green part changes
according to the parameters.
The frequency and voltage differences are indicated on top of the bargraphs.
Symbol/Softkey
Description
Operating mode MANUAL: Raise voltage/frequency.
Operating mode MANUAL: Lower voltage/frequency.
145
easYgen-3000XT Series
B37574
4 Configuration
4.1.5.10 Synchroscope busbar/mains