Relay
Application mode
No.
Terminal
None
A01
GCB open
A02
GCB
A03
GCB/MCB
A04
[R 12]
59/60
LogicsManager; pre-assigned with 'Alarm class C, D, E, F active'
Table 46: Internal relay outputs - assignment
CAUTION!
Uncontrolled operation due to faulty configuration
The discrete output "Ready for operation" must be wired in series with an emergency
stop function.
This means that it must be ensured that the generator circuit breaker is opened and the
engine is stopped if this discrete output is de-energized.
If the availability of the plant is important, this fault must be signaled independently from
the unit.
ID
Parameter
CL
Setting range
[Default]
Description
12580
Ready for op. OFF
(Ready for operation
OFF)
2
Determined by LogicsManager
99.01
[(0 & 0) & 1]
= 11870
The "Ready for operation" relay is
energized by default if the power
supply exceeds 8 V.
Once the conditions of the Logics‐
Manager have been fulfilled, the
relay will be de-energized. This
LogicsManager output may be
configured with additional
conditions, which may signal a
PLC an "out of operation"
condition by de-energizing the
relay on terminals 41/42, like
"shutdown alarm" or no "AUTO
mode" present.
Notes
For information on the Logics‐
Manager and its default settings
see
.
12110
(See ID
table
below)
Relay 2
For (pre-defined)
function see assignment
table above)
2
Determined by LogicsManager
99.02
[(03.05 Horn & 1) & 1]
= 11871
Once the conditions of the Logics‐
Manager have been fulfilled, the
relay will be energized.
Notes
For information on the Logics‐
Manager and its default settings
see
.
239
easYgen-3000XT Series
B37574
4 Configuration
4.4.2.3 Discrete Outputs (LogicsManager)
Released