Task
Formula
(except dynamic setpoint is not matched)
Mains Parallel Operation (Import/Export Control)
Starting the First Engine Combination
(no engine supplies the busbar)
PMN
setpoint
– PMN
real
+ PGN
real active
> PMOP
minimum
Changing the Engine Combination to Increase Rated Power
PGN
real active
> P
max. load parallel
Changing the Engine Combination to Reduce Rated Power
(except dynamic setpoint is not matched)
PGN
real active
< P
min. load parallel
Stopping the Last Engine Combination (load close to
minimum load)
PMN setpoint – PMN
real
+ PGN
real active
< PMOP
minimum
–
P
hysteresis
MOP
LDSS dynamic
Dynamic characteristic
= [(max. generator load – min. generator load) * dynamic] + (min. generator
load)
Dynamic power level
= (dynamic characteristic) * (generator rated power)
Constants
Low dynamic
= 25 %
Moderate
dynamic
= 50 %
High dynamic
= 75 %
☼
Example for moderate dynamic
• Dynamic characteristic = [(80 % – 40 %) * 50 %] + (40 %) = 60 %
•
• Dynamic power level = (60 %) * (200 kW) = 120 kW
•
1196
easYgen-3000XT Series
B37574
9 Appendix
9.6.2 Load Dependent Start Stop (LDSS) Formulas