ID
Parameter
CL
Setting range
[Default]
Description
5815
Hysteresis lower
voltage limit
2
0 to 50%
[2%]
If the mains voltage has fallen
below the limit configured in
parameter
must exceed the limit and the
value configured here, to be
considered as being within the
operating limits again.
5812
Upper frequency limit
2
66.7¹ to 150.0%
[110.0%]
The maximum permissible
positive deviation of the mains
frequency from the rated system
frequency (parameter
is configured here.
This value may be used as a
frequency limit switch. The
conditional state of this switch
may be used as a command
variable for the LogicsManager
(02.10).
Notes
¹ The lowest measurable
frequency is 40 Hz.
66.7 % of 60 Hz is 40 Hz.
Equivalent for 50 Hz don't go
below 80 %.
5816
Hyst. upper
frequency limit
2
0.0 to 50.0%
[0.5%]
If the mains frequency has
exceeded the limit configured in
parameter
frequency must fall below the limit
and the value configured here, to
be considered as being within the
operating limits again.
5813
Lower frequency limit
2
66.7¹ to 100.0%
[90.0%]
The maximum permissible
negative deviation of the mains
frequency from the rated system
frequency (parameter
is configured here. This value may
be used as a frequency limit
switch. The conditional state of
this switch may be used as a
command variable for the
LogicsManager (02.10).
Notes
¹ The lowest measurable
frequency is 40 Hz.
66.7 % of 60 Hz is 40 Hz.
Equivalent for 50 Hz don't go
below 80 %.
5817
Hyst. lower
frequency limit
2
0.0 to 50.0%
[0.5%]
If the mains frequency has
exceeded the limit configured in
parameter
frequency must raise above the
limit and the value configured
here, to be considered as being
within the operating limits again.
488
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.3.1 General Mains Operating Range
Released