Remote voltage setpoint
Object 21FEh (Parameter 510)
This value may be used as data source "[05.59] Interface V setp [V]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the voltage setpoint for voltage control.
The data type is UNSIGNED32.
The value is scaled in [V].
Example
• 400 V » 400 = 190h
•
• 10000 V » 10000 = 2710h
•
Remote reactive power setpoint
Object 21FFh (Parameter 511)
This value may be used as data source "[05.83] Interf.kvar sp [kvar]" via the
AnalogManager. No password is required to write this value. This object is required to
transmit the reactive power setpoint for the kvar control.
The data type is signed INTEGER32.
The value is scaled in [kvar*10].
Examples:
• 100.0 kvar » 1000 = 3E8h
•
• 100.2 kvar » 1002 = 3EAh
•
Q(V) voltage shift VQ0
Object 2200h (Parameter 512)
This is the Setpoint for the reactive power - voltage function Q(V). [VDE-AR-N 4110]
Interface reference value VQ0 has the resolution of (1/100) steps. The “starting” value is
1.00. A value limitation is included.
1069
easYgen-3000XT Series
B37574
9 Appendix
9.2.9.1 Receive Data (sent from remote control to the easYgen)