Message text
ID
Meaning
The generator power has exceeded the limit value 2 for generator overload in
mains parallel operation.
Unbalanced load 1
2412
Generator unbalanced load, limit value 1
The generator current has exceeded the limit value 1 for generator unbalanced
load.
Unbalanced load 2
2413
Generator unbalanced load, limit value 2
The generator current has exceeded the limit value 2 for generator unbalanced
load.
Gen. volt. asymmetry
3907
Voltage asymmetry
The generator phase-to-phase voltages have higher differences between each
other than the configured limit value.
Ground fault 1
3263
Generator ground current, limit value 1
The measured or calculated ground current has exceeded the limit value 1 for the
generator ground current.
Ground fault 2
3264
Generator ground current, limit value 2
The measured or calculated ground current has exceeded the limit value 2 for the
generator ground current.
Gen.ph.rot. mismatch
3955
Generator rotating field mismatch
The generator rotating field does not correspond with the configured direction.
Gen. PF lagging 1
2337
Generator overexcited, limit value 1
The power factor limit 1 has been exceeded at the generator towards inductive.
Gen. PF lagging 2
2338
Generator overexcited, limit value 2
The power factor limit 2 has been exceeded at the generator towards inductive.
Gen. PF leading 1
2387
Generator underexcited, limit value 1
The power factor limit 1 has fallen below at the generator towards capacitive.
Gen. PF leading 2
2388
Generator underexcited, limit value 2
The power factor limit 2 has fallen below at the generator towards capacitive.
Gen.act.pwr.mismatch
2924
Generator active power mismatch
The deviation between the generator power and the active power setpoint has
exceeded the limit.
Gen. unloading fault
3124
Generator unloading mismatch
The easYgen failed to reduce the generator power below the configured unload
limit.
Pole slip
2424
Pole slip Monitoring Alarm active
A pole slip was detected during running the generator mains parallel.
1181
easYgen-3000XT Series
B37574
9 Appendix
9.5.5.3 Generator monitoring
Released