HMI Text
Note
08.40 J1939 dev. 3 timeout
CAN J1939 device 3 timeout
08.43 Syst.update easYgen
System update easYgen
There is an easYgen detected in the communication network which is not taught in
(A system update is required)
08.45 CPU overload R1 trip
CPU overload R1 trip
(alarm class B, not selfackn.) becomes active if CPU overload is longer than 10s.
08.46 GCB failure 50BF
GCB failure 50BF
08.47 MCB failure 50BF
MCB failure 50BF
08.48 MCB plausibility
MCB plausibility
08.50 Syst.upd.r/y twinkle
System update red or yellow LED twinkling
Red twinkle: if there is no device recognized according to the last system update.
Yellow twinkle: if there is no device detected according to the last system update
on one redundant interface. (This is no alarm, only a LM.)
08.51 CAN LS fault
CAN loadshare fault if load sharing with CAN is selected and no device detected.
(This is no alarm, only a LM.)
08.52 Ethernet A LS fault
Ethernet A loadshare fault if load sharing with Ethernet A is selected and no device
detected. (This is no alarm, only a LM.)
08.62 Ethernet issue
Ethernet issue
(E.g. broadcast storm)
08.70 CAN EthA redundancy
Load share interface redundancy CAN1 / Ethernet A lost
08.71 PV disconnect
PV disconnect level under run
08.72 Modbus dev.1 timeout
Modbus Master communication timeout device 1 (This is no alarm, only a LM.)
08.73 Modbus dev.2 timeout
Modbus Master communication timeout device 2 (This is no alarm, only a LM.)
08.74 Modbus dev.3 timeout
Modbus Master communication timeout device 3 (This is no alarm, only a LM.)
08.75 Modbus dev.4 timeout
Modbus Master communication timeout device 4 (This is no alarm, only a LM.)
08.76 Modbus dev.5 timeout
Modbus Master communication timeout device 5 (This is no alarm, only a LM.)
08.77 J1939 AVR timeout
CAN J1939 AVR timeout or (only for AVRbridge-10-P1) remote configuration error
08.78 easYgen LS timeout
No received loadshare message for a specified timeout of any teached in easYgen
08.80 Redundancy LS timeout
No received loadshare message (of one of the redundant interfaces) for a specified
timeout of any teached in device
9.3.2.9
Group 09: Alarms discrete inputs
TRUE if the alarm is active or latched.
HMI Text
Note
09.01 Discrete input 1
09.02 Discrete input 2
09.03 Discrete input 3
09.04 Discrete input 4
1096
easYgen-3000XT Series
B37574
9 Appendix
9.3.2.9 Group 09: Alarms discrete inputs
Released