Power measurement example
☼
How to use Power exponent 3181
Power measurement:
• The measurement range is 0…250 kW
•
• Momentary measurement value = 198.5 kW (198.500 W)
•
Setting
value
3181
Meaning
Calculation
Transfer value
(16 Bit, max. 32767)
Possible
display
format
2
10
2
198500 W / 10
2
W
1985
198.5 kW
3
10
3
198500 W / 10
3
W
198
198 kW
4
10
4
198500 W / 10
4
W
19
N/A
5
10
5
198500 W / 10
5
W
1
N/A
Table 82: Power measurement example
Voltage measurement example
☼
How to use Voltage exponent 3182
Voltage measurement:
• The measurement range is 0…480 V
•
• Momentary measurement value = 477.8 V
•
Setting
Meaning
Calculation
Transfer value
(16 Bit, max. 32767)
Possible
display
format
-1
10
-1
477.8 V / 10
-1
W
4778
477.8 V
0
10
0
477.8 V / 10
0
V
477
477 V
1
10
1
477.8 V / 10
1
V
47
N/A
2
10
2
477.8 V / 10
2
V
4
N/A
Table 83: Voltage measurement example
604
easYgen-3000XT Series
B37574
4 Configuration
4.7.3 Modbus Protocol