indicates "System Update easYgen" and the logical command variables "08.43" and
"08.65" will be enabled.
For more information see
╚═▷ “6.2.2 Communication Management”
ID
Parameter
CL
Setting range
[Default]
Description
7832
Monitoring
2
[On]
Enabling to monitor the system if
there are more devices against
latest updated system
configuration.
Notes
To detect less easYgen devices
against latest updated system
configuration use missing member
monitor
.
Off
Monitoring is disabled.
7833
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
7834
Self acknowledge
-/-
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
Table 79: Parameter setting: Monitoring system update
4.5.6.19 Operating Range Failure
General notes
The operating range failure monitoring issues an Operating Range Failure Alarm
"Oper.range failed XX" (where XX is the number of Check 01 to 12) if one of the following
conditions is fulfilled. Example: Check 4 failed causes »Oper.range failed 4«.
Only the first incoming operation range failure will tripp an alarm. Because in most cases
this will be the root cause for eventually incoming further operating range alarms. Any
other operating range alarm can only be tripped if there is no active or latched operating
range alarm.
581
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.19 Operating Range Failure
Released