Modbus-
Address
Size
Index
Description
Unit
Scale
Model
50323
int16
15694
Emission inducement failure reason (Scania
S8)
0: OK
1: Dosing Error
2: Urea Quality
3: Monitor Failure
4: Nox Failure
5-13: Reserved for future assignment by
Scania
14: Error
15: Not available
Mask: F000h
All
SPN 6918 SCR System Cleaning Inhibited Due
to Inhibit Switch
0: not inhibited
1: inhibited
2: reserved for SAE assignment
3: not available
Mask: 0C00h
All
12050
SPN 6915 SCR System Cleaning Lamp
Command
0:Off
1: On – solid
2: reserved for SAE assignment
3: reserved for SAE assignment
4: On – fast blink (1 HZ)
5: reserved for SAE assignment
6: reserved for SAE assignment
7: not available
Mask: 0380h
All
15505
SPN 3698 Exhaust System High Temperature
Lamp Command
0: Off
1: On – solid
2: reserved for SAE assignment
3: reserved for SAE assignment
4: reserved for SAE assignment
5: reserved for SAE assignment
6: reserved for SAE assignment
7: not available
Mask: 0070h
All
12049
SPN 4332 Aftertreatment 1 SCR System State
0: Dormant (sleep mode)
Mask: 000Fh
All
1034
easYgen-3000XT Series
B37574
9 Appendix
9.2.7 Protocol 5016 (Basic Visualization)