Modbus-
Address
Size
Index
Description
Unit
Scale
Model
1: Preparing dosing readiness
2: Normal dosing operation
3: System error pending
4: Reserved for future assignment by SAE
5: Protect mode against heat (pressure
buildup)
6: Protect mode against cold (defreeze)
7: Shutoff (wait for afterrun)
8: Diagnosis (afterrun)
9: Service test mode, dosing allowed
10: Service test mode, dosing not allowed
11-13: Reserved for future assignment by SAE
14: Error
15: Not available
50324
int16
Internal
Mask: 8000h
All
SPN 4991: Charger 1 power line state
0: Disconnected
1: Connected
2: Error
3: Not Available
Mask: 6000h
All
SPN 4990: Charger 1 state
0: Idling
1: Charging
2: Stand-by
3 - 12: Reserve
13: Battery failure
14: Charger failure
15: Not Available
Mask: 1E00h
All
15696
HC Evaporation required action(Scania S8)
0: No action required
1: Run engine warm
2: Increased idle and heavy exhaust braking
3: Engine stop
4,5: Reserved
6: Error
7: Not Available
Mask: 01C0h
All
12048
SPN 5246 Aftertreatment SCR Operator
Inducement Severity
Mask: 0038h
All
1035
easYgen-3000XT Series
B37574
9 Appendix
9.2.7 Protocol 5016 (Basic Visualization)
Released