Example
Six gensets (G1 through G6) supply a system with two group breakers (A, B) as shown
in . All gensets have the same segment number configured #1 (parameter
)
Fig. 170:
Load sharing - grouping
Case I
Group breakers A and B are closed and G1 through G6 supply the same
busbar. The same segment number is configured to each genset since
all gensets supply the same busbar.
Case II
Group breaker A is closed and group breaker B is open (G1 through G4
supply a different busbar than G5 and G6). A different segment number
must be selected for G5 and G6 by enabling the LogicsManager
function "Segment no.2 act" (parameter
) in order to change
the segment number of G5 and G6 to #2.
Case III
Group breakers A and B are open (G1 and G2, G3 and G4, as well as G5
and G6 supply different busbars).
A different segment number must be selected for G3 and G4
(LogicsManager function "Segment no.2 act" (parameter
))
as well as to G5 and G6 (LogicsManager function "Segment no.3 act"
(parameter
)).
With this, the segment number of G3 and G4 is changed to #2 and the
segment number of G5 and G6 is changed to #3.
ID
Parameter
CL
Setting range
[Default]
Description
1723
Segment number
2
1 to 32
[1]
The genset is assigned a load
share segment number with this
parameter. This segment number
may be overridden by the
following parameters
.
12929
Segment no.2 act.
2
Determined by LogicsManager
86.87
Once the conditions of the
LogicsManager have been fulfilled,
this genset is assigned load share
segment number 2 (this
336
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.3.8 Load Share Control Grouping
Released