Remote active power setpoint
Object 21FBh (Parameter 507)
This value may be used as data source "[05.56] Interface P setp [kW]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the active power setpoint for active power control.
The data type is INTEGER32.
The value is scaled in [kW * 10].
Example
• 100 kW = 1000 = 03E8h
•
Remote power factor setpoint
Object 21FCh (Parameter 508)
This value may be used as data source "[05.12] Interface PF sp [%]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the power factor setpoint for power factor control.
The data type is INTEGER16.
The valid range for this value is [-710 to 1000 to 710].
Example
• PF (cosphi) = c0.71 (capacitive) = -710 = FD3Ah
•
• PF (cosphi) = 1.00 = 1000 = 03E8h
•
• PF (cosphi) = i0.71 (inductive) = 710 = 02C6h
•
Remote Frequency Setpoint - Object 21FDh
Remote frequency setpoint
Object 21FDh (Parameter 509)
This value may be used as data source "[05.53] Interface f setp [Hz]" via the
AnalogManager. No password is required to write this value.
This object is required to transmit the frequency setpoint for frequency control.
The data type is INTEGER16.
The valid range for this value is [Hz * 100].
Example
• 50.00 Hz = 5000 = 1388h
•