Modbus-
Address
Size
Index
Description
Unit
Scale
Model
03.21 3-Pos. Controller Freq./Power lower
Mask: 4000h
All
03.22 3-Pos. Controller Volt./ReactPow raise
Mask: 2000h
All
03.23 3-Pos. Controller Volt./ReactPow lower
Mask: 1000h
All
04.06 GCB is closed
Mask: 0800h
All
04.07 MCB is closed
Mask: 0400h
All
05.16 Derating active (J1939 or freely)
Mask: 0200h
All
04.18 Synchronisation GCB procedure is active
Mask: 0100h
All
04.19 Opening GCB relay is active
Mask: 0080h
All
04.20 Close command GCB is active
Mask: 0040h
All
04.21 Synchronisation MCB procedure is active
Mask: 0020h
All
04.22 Open command MCB is active
Mask: 0010h
All
04.23 Close command MCB is active
Mask: 0008h
All
04.28 Unloading generator is active
Mask: 0004h
All
04.29 Unloading mains is active
Mask: 0002h
All
04.30 Power limited prerun
Mask: 0001h
All
50105
uint16
4156
BITLIST ControlBits4
04.16 GGB is closed
Mask: 8000h
EG3500XT-P1
EG3500XT-P2
04.17 GGB is released
Mask: 4000h
EG3500XT-P1
EG3500XT-P2
04.24 Synchronisation GGB procedure is active
Mask: 2000h
EG3500XT-P1
EG3500XT-P2
04.25 Open command GGB is active
Mask: 1000h
EG3500XT-P1
EG3500XT-P2
04.26 Close command GGB is active
Mask: 0800h
EG3500XT-P1
EG3500XT-P2
Dead busbar closure requ. for GCB,MCB or
GGB
Mask: 0400h
All
4.62 Active power load share is active
Mask: 0200h
All
4.63 Reactive power load share is active
Mask: 0100h
All
Generator with a closed GCB is requested
Mask: 0080h
All
LDSS: The Engine shall start
Mask: 0040h
All
LDSS: The Engine shall stop
Mask: 0020h
All
LDSS: The Engine shall stop, if possible
Mask: 0010h
All
LDSS: Minimum Running Time is active
Mask: 0008h
All
04.43 The LDSS function is active
Mask: 0004h
All
998
easYgen-3000XT Series
B37574
9 Appendix
9.2.7 Protocol 5016 (Basic Visualization)
Released