To control the PV inverter, the easYgen3000XT calculates next:
• The AM variable 10.39 PV load ref. [%] (PV set-point value 0% - 100%, can be
•
transferred to the PV inverter over an analog output)
• LM command variables (in applications using discrete load steps these LMs can be
•
transferred to the PV inverter over several digital outputs):
◦ 04.74 PV load ref. 0%
◦
◦ 04.75 PV load ref. 30%
◦
◦ 04.76 PV load ref. 60%
◦
◦ 04.77 PV load ref. 100%
◦
In addition, the variable ”10.39 PV load ref. [%]“ (ID 9766) can be sent to the PV inverter
via MODBUS TCP using the MODBUS MASTER (
easYgen3000XT. It is indicated also in ToolKit with a gauge.
The regulation output (analog or in steps) is treated as follows:
• If the Function is disabled (by parameter
), the output "10.39 PV load ref.
•
[%]" is 0%.
• If the Function is enabled and LM ”Release PV regulation“ (parameter
•
FALSE, the output 10.39 PV load ref. [%] is 100% and 04.77 PV load ref. 100% is
TRUE.
• If the Function is enabled and LM ”Release PV regulation“ (parameter
•
TRUE, the output 10.39 PV load ref. [%] shows the current PID value and the
corresponding LM "PV load ref." is TRUE.
To provide a proper function the PV reduction must be tracked slowly. Reverse power of
the generator must lead to an instant cut of the PV load.