Overview PV load reduction regulated mode
GCB
G
=
~
Breaker feedback
3ph voltage
3ph current
1(3) ph voltage
3 Digital outputs
(+/-20mA; +/-10V)
Modbus TCP
0%; 30%; 60%; 100%
power
0%...100% power
0%...100% power
PV
Inverter
P
PV
load
Photovoltaic
Load Reduction
Logics &
Analog-
Manager
AC
measurement
DI/DO
AO
Com
CANopen
Com
Modbus
Master
PID
Regulation
Genset
control
algorithm
HMI
EG3000XT
Fig. 175:
Overview PV load reduction regulated mode
Parameter
Navigate to [Parameter / Configuration / Configure application / Configure controller /
Miscellaneous / PV load reference].
ID
Parameter
CL
Setting range
[Default]
Description
8911
PV load reference
2
[Off]
The function is disabled. The
output value remains 0%.
Regulated
The PV load reference function is
enabled. If LogicsManager 8928 is
true too, the PV function with the
minimum load setpoint configured
by AnalogManager 8914 becomes
active.
8928
Release PV
regulation
2
Determined by LogicsManager
87.80
[(0 & 1) & 1]
If this LogicsManager condition is
TRUE and 8911 is ”Regulated“,
the PV regulation becomes active.
If this LogicsManager condition is
FALSE and 8911 is ”Regulated“,
the regulation output 10.39 PV
load ref. [%] goes on 100% and
the load step "04.77 PV load ref.
100%" goes TRUE.
8917
Proportional gain
2
0.01 to 50.00
[5.00]
The proportional coefficient
specifies the gain. By increasing
the gain, the response is
increased to permit larger
corrections to the variable to be
controlled.
The farther out of tolerance the
process is the larger the response
373
easYgen-3000XT Series
B37574
4 Configuration
4.4.4.5.6 Photovoltaic (PV) load reduction regulated mode
Released