Generator Reactive Power Limitations
A reactive power control (kvar or power factor) can cause an overload or damage of the
generator. To avoid this the easYgen provides a 2-step protection:
⚙
1. ▷
The own absolute generator current is monitored with an percentage setting related to
rated current input (ID
). The easYgen limits or controls down the excitation
) is not exceeded.
2. ▷
The inductive reactive power outcome of the own generator is limited according to the
configuration of ID
.
Or:
The inductive reactive power income of the own generator is limited according to the
configuration of ID
.
Fig. 161:
The kvar setpoint is limited to protect the generator
Tracking of the limitation
An active Limitation is
• indicated as 'Gen excitation lim.' on the display (HMI)
•
• driving the LogicsManager command variable 02.38 Gen excitation lim. from FALSE
•
to TRUE
• driving an event logger entry
•