Example 2: Addressing the generator voltage measuring
ID
Parameter
Setting range
Data type
1851
Generator voltage measuring
3Ph 4W
3Ph 3W
1Ph 2W
1Ph 3W
3Ph 4W OD
UNSIGNED 16
☼
Example
• Modbus address = 40000 + (Par. ID + 1) = 41852
•
• Modbus length = 1 (UNSIGNED 16)
•
If the setting range contains a list of parameter settings like in this example, the
parameter settings are numbered and start with 0 for the first parameter setting. The
number corresponding with the respective parameter setting must be configured.
⚙
1. ▷
Fig. 305:
Modscan32 at address 41852
Set the configuration to address parameter 1851 as shown in (
).
▶
The parameter is configured to "3Ph 4W".
6.5.2.2
Configuration Of LogicsManager Functions
Next to HMI and ToolKit, LogicsManager can also be configured via Modbus.
• The complete LogicsManager instruction set is available for Modbus control.
•
• Hex code equivalents are defined for all LogicsManager settings.
•
• The Modbus definition for a LogicsManager equation consists of 7 data words
•
following a well defined sequence.