If this protective function is triggered, the display indicates "Amber warning lamp" and
the logical command variable "05.14" will be enabled.
ID
Parameter
CL
Setting range
[Default]
Description
15120
Monitoring
2
On
Monitoring of the Amber Warning
Lamp message from the ECU is
carried out according to the
following parameters.
[Off]
Monitoring is disabled.
15124
Delay
2
0 to 999 s
[2 s]
The amber warning lamp delay is
configured with this parameter.
If the ECU sends the Amber
Warning Lamp On message, the
action specified by the alarm class
is initiated after the delay
configured here expires.
15121
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class A]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
15122
Self acknowledge
2
[Yes]
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
15123
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
568
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.8 J1939 Interface - Amber Warning Alarm
Released