Set easYgen-XT to code level CL05 via Modbus TCP
With factory settings username is expected to be "CL05" and password to be "CL0500"
for code level CL05. With setting the Code Level all five communication channels
(sockets) are released.
⚙
1. ▷
Write and transfer »CL05« as hex:
43-4C-30-35-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-
00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00
for "User name" to parameter
2. ▷
Write and transfer »CL0500« as hex:
43-4C-30-35-30-30-00-00-00-00-00-00-00-00-00-00-00-00-00-00-
00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00-00
for "Password" to parameter 7491 (40 bytes).
▶
Code level can be read with parameter 10427
The password level is visible in the Ethernet interface diagnostic screen.
Password handling via Modbus using RS-485 connection
The easYgen must be a member of a RS-485 network and the password has to be
transferred (from PLC) to the device.
☼
Set easYgen-XT to code level 5 via Modbus RS-485
With factory settings the password is expected to be "500" for code level 5.
• Modbus address = (Par. ID + 1) = 410431
•
• Modbus length = 1 (UNSIGNED 16)
•
Code level state can be read with parameter 10420.
Please find the password level in ToolKit: [STATUS MENU / Diagnostic / Interfaces /
RS485].
Password handling via CAN using CANopen connection
The easYgen must be a member of a CANopen network and the password has to be
transferred (from PLC) to the device.
The easYgen provides several CAN ports and therefore each port has his own password
level. The password is written by a SDO Communication Channel.
☼
Set easYgen-XT to code level 5 via CANopen
With factory settings the password is expected to be "500" for code level 5.
187
easYgen-3000XT Series
B37574
4 Configuration
4.3.4 Enter Password
Released