ID
Parameter
CL
Setting range
[Default]
Description
Pre-excitation time = Starter time
+ Pre-excitation D+ off delay time
3310
Ignition delay
(Gas Engine only)
2
0 to 9999 s
[5 s]
With gas engines often a purging
operation is desired before
starting.
With the engaging of the starter
the ignition delay is started. The
display indicates "Turning".
If the "Minimum speed for
ignition" is reached after the
expiration of this time, the ignition
is energized.
3311
Gas valve delay
(Gas Engine only)
2
1 to 999 s
[5 s]
By energizing the ignition relay
the gas valve delay is started
("Ignition" is displayed).
After the time set here has
expired, and as long as the speed
is higher than the minimum speed
for ignition, the gas valve is
enabled for the time configured in
parameter
time" ("Start" is displayed).
Once the ignition speed has been
reached, the gas valve remains
opened. If the speed falls below
ignition speed, the gas valve will
be closed and the "Ignition" relay
is de-energized 5 seconds later.
3312
Minimum speed for
ignition
(Gas Engine only)
2
10 to 1,800 rpm
[100 rpm]
After expiration of the ignition
delay the number of revolutions
set here must be reached, so the
"Ignition" relay will be energized.
208
easYgen-3000XT Series
B37574
4 Configuration
4.4.1.1 Configure Engine (general)
Released