Example of a Time Dependent Mains Voltage Curve
Fig. 194:
Time-dependent voltage monitoring curve
P1
0.00 s → 45.0%
P2
0.15 s → 45.0%
P3
0.15 s → 70.0%
P4
0.70 s → 70.0%
P5
1.50 s → 90.0%
P6
3.00 s → 90.0%
P7
4.00 s → 90.0%
Fallback
threshold
90.0%
Initial
threshold
80.0%
Fallback
time
1.00 s
General settings for Mains decoupling and Monitoring Voltage 1 - 3
Find parameters ...
Find parameters in two menus:
• [Configuration / Configure monitoring / Mains decoupling / General mains
•
decoupling]
• [Configuration / Configure monitoring / Mains / Frequency / Voltage / Mains time-
•
dependent voltage]
510
easYgen-3000XT Series
B37574
4 Configuration
4.5.3.10 Mains Time-Dependent Voltage
Released