ID
Parameter
CL
Setting range
[Default]
Description
No
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
15193
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
Table 77: J1939 Monitoring: Device 3
4.5.6.7
J1939 Interface - Red (Stop) Alarm
General notes
This monitor monitors, whether a specific alarm bit is received from the CAN J1939
interface. This enables to configure the easYgen in a way that a reaction is caused by this
bit (e.g. warning, shutdown).
If this protective function is triggered, the display indicates "Red stop lamp" and the
logical command variable "05.13" will be enabled.
ID
Parameter
CL
Setting range
[Default]
Description
15115
Monitoring
2
On
Monitoring of the Red Stop Lamp
message from the ECU is carried
out according to the following
parameters.
[Off]
Monitoring is disabled.
15119
Delay
2
0 to 999 s
[2 s]
The red stop lamp delay is
configured with this parameter.
566
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.7 J1939 Interface - Red (Stop) Alarm