ID
Parameter
CL
Setting range
[Default]
Description
This value refers to the Generator
rated active power (parameter
2255
2261
Delay
2
0.02 to 99.99 s
2255: [5.00 s]
2261: [5.00 s]
If the monitored generator power
falls below the threshold value for
the delay time configured here, an
alarm will be issued.
Notes
If the monitored generator power
exceeds or falls below the
threshold (plus/minus the
hysteresis) again before the delay
expires the time will be reset.
2251
2257
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
2251: [Class B]
2257: [Class F]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
2252
2258
Self acknowledge
2
4
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
2253
2259
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
446
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.3 Generator Reverse/Reduced Power (Level 1 & 2) ANSI# 32R/F
Released