6.3.2
Configuring A Setpoint Control Via Analog Input
The following example illustrates how to configure an easYgen to use an external load
setpoint via analog input [AI 03].
The external setpoint may be enabled using a switch, wired to discrete input [DI 09].
An analog 0 to 20 mA input is to be used where 4 mA corresponds with 0 % power
(0 MW), 12 mA corresponds with 50 % power (1 MW), and 20 mA corresponds with 100 %
power (2 MW).
Configuring the rated generator power
⚙
1. ▷
Either on the front panel or using ToolKit navigate to menu [Configure measurement].
2. ▷
Configure the parameter listed in
.
ID
Parameter
Value
Comment
1752
Gen. rated
active
power [kW]
2000
Generator rated power of 2 MW
Table 101: Parameters for rated generator power
Configuring the analog input for real power setpoint
⚙
1. ▷
Either on the front panel or using ToolKit navigate to menu [Parameter / Configuration /
Configure application / Configure inputs/outputs / Configure analog inputs / Analog input
3].
2. ▷
Configure the parameters listed below.
ID
Parameter
Value
Comment
1100
Type
Linearr
A user-defined linear characteristic curve is to be used
1101
User
defined
min display
value
+0.00e0
A value of 0.00 is displayed at the minimum of the input
range
1102
User
defined
max
+2000.00e3
A value of 2000.00e3 (= 2000000) is displayed at the
maximum of the input range