ID
Parameter
CL
Setting range
[Default]
Description
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
4203
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4206
AM FlexLim 1 source
2
Determined by AnalogManager
82.01
[A1 = 10.01 ZERO]
Any possible data sources may be
selected. Analog and digital OUT
value/signal are available as
sources for AnalogManager and
LogicsManager.
for a list of all data sources.
Parameter IDs
Flexible
limit #
Descrip‐
tion
Monitor‐
ing
Monitor‐
ed
analog
value
Monitor‐
ing at
Limit
Hyster‐
esis
Delay
Alarm
class
Self
acknow‐
ledge
Enabled
Fallback
1
4208
4200
4206
4204
4205
4216
4207
4201
4202
4203
2
4225
4217
4223
4221
4222
4233
4224
4218
4219
4220
3
4242
4234
4240
4238
4239
4250
4241
4235
4236
4237
4
4259
4251
4257
4255
4256
4267
4258
4252
4253
4254
5
7108
4270
4276
4274
4275
4278
4277
4271
4272
4273
6
7116
4280
4286
4284
4285
4288
4287
4281
4282
4283
7
7124
4290
4296
4294
4295
4298
4297
4291
4292
4293
8
7132
6000
6006
6004
6005
6008
6007
6001
6002
6003
9
7140
6010
6016
6014
6015
6018
6017
6011
6012
6013
10
7148
6020
6026
6024
6025
6028
6027
6021
6022
6023
11
7156
6030
6036
6034
6035
6038
6037
6031
6032
6033
12
7164
6040
6046
6044
6045
6048
6047
6041
6042
6043
13
7172
6050
6056
6054
6055
6058
6057
6051
6052
6053
14
7180
6060
6066
6064
6065
6068
6067
6061
6062
6062
552
easYgen-3000XT Series
B37574
4 Configuration
4.5.5 Flexible Limits
Released