9.4.2
Data Sources AM
9.4.2.1
Group 01: Generator values
The percentage value is related on the following values:
• generator rated voltage
• system rated frequency
• generator rated current
• power factor:
Lagging: value [%] = (2 - PF) * 50%
e.g. PF = 0.8: value [%] = (2 - 0.8) * 50% = 60%
Leading: value [%] = PF * (-1) * 50%
e.g. PF = - 0.8: value [%] = (- 0.8) * (-1) * 50% = 40%
• generator rated active power
• generator rated reactive power
• generator rated active and generator rated reactive power
HMI Text
Note
01.01 Gen.volt.L-N [%]
Generator voltage wye average
01.02 Gen.volt.L1-N [%]
Generator voltage L1-N
01.03 Gen.volt.L2-N [%]
Generator voltage L2-N
01.04 Gen.volt.L3-N [%]
Generator voltage L3-N
01.05 Gen.volt.L-L [%]
Generator voltage delta average
01.06 Gen.volt.L1-L2 [%]
Generator voltage L1-L2
01.07 Gen.volt.L2-L3 [%]
Generator voltage L2-L3
01.08 Gen.volt.L3-L1 [%]
Generator voltage L3-L1
01.09 Gen.frequency [%]
Generator frequency
01.10 Gen.freq.L1-L2 [%]
Generator frequency L1-L2
01.11 Gen.freq.L2-L3 [%]
Generator frequency L2-L3
01.12 Gen.freq.L3-L1 [%]
Generator frequency L3-L1
01.13 Gen.current [%]
Generator average current
01.14 Gen.current L1 [%]
Generator current L1
01.15 Gen.current L2 [%]
Generator current L2
01.16 Gen.current L3 [%]
Generator current L3
01.17 Gen.curr.max. L1 [%]
Dragged generator current L1
01.18 Gen.curr.max. L2 [%]
Dragged generator current L2
01.19 Gen.curr.max. L3 [%]
Dragged generator current L3
01.20 Gen. PF [%]
Generator power factor
1139
easYgen-3000XT Series
B37574
9 Appendix
9.4.2 Data Sources AM
Released