These values can be assigned to the analog
variables of the Customer screens for
visualization.
81.30 AM Consumer load [kW]
This analog variable provides the load for the LDDS
with load prediction in internal source mode.
6.3.15.4 Tables
RPDO Summary
RPDO configuration to get data from ATS 1:
Receive PDO
Database Index
AnalogManager variable
Comment
RPDO1 Word1
3371
21.01 CAN1 RPDO1.1
Binary information
RPDO1 Word2
3372
21.02 CAN1 RPDO1.2
Real power [0.1kW]
RPDO Summary
RPDO configuration to get data from ATS 2:
Receive PDO
Database Index
AnalogManager variable
Comment
RPDO2 Word1
3375
21.05 CAN1 RPDO2.1
Binary information
RPDO2 Word2
3376
21.06 CAN1 RPDO2.2
Real power [0.1kW]
RPDO Summary
RPDO configuration to get data from ATS 3:
Receive PDO
Database Index
AnalogManager variable
Comment
RPDO3 Word1
3379
21.09 CAN1 RPDO3.1
Binary information
RPDO3 Word2
3380
21.10 CAN1 RPDO3.2
Real power [0.1kW]
RPDO Summary
RPDO configuration to get data from ATS 4:
Receive PDO
Database Index
AnalogManager variable
Comment
RPDO4 Word1
3383
21.13 CAN1 RPDO4.1
Binary information
RPDO4 Word2
3384
21.14 CAN1 RPDO4.2
Real power [0.1kW]
RPDO Summary
RPDO configuration to get data from ATS 5:
Receive PDO
Database Index
AnalogManager variable
Comment
RPDO5 Word1
3387
21.17 CAN1 RPDO5.1
Binary information
RPDO5 Word2
3388
21.18 CAN1 RPDO5.2
Real power [0.1kW]
762
easYgen-3000XT Series
B37574
6 Application Field
6.3.15.4 Tables
Released