LogicsManager function "Operat. mode STOP"
The LogicsManager function "Operat. mode STOP" (parameter
configured as shown in (
).
▶
STOP operation mode is enabled as soon as discrete input 10 is de-energized.
6.3.5.2
Setting Up A Test With Or Without Load
There are a lot of different opinions of the behavior of a proper test mode. The easYgen
controller is supporting the following two modes:
• Test with load
•
• Test without load
•
Alternatives to the operation mode TEST
In cases the dedicated TEST operation mode shall be not taken, the following procedure
can be taken to execute an TEST run in the operation mode AUTOMATIC.
Test with load
This is the LogicsManager function Start req. in AUTO (parameter
message appears on the display.
If the mains fail during start in auto, the unit keeps running until the mains return and the
mains settling time is expired or the conditions for Start req. in AUTO are FALSE again.
The result depends on which condition is active longer.