Mains power [kW] from ATS (Word 2)
The word with mains power is an 16INT signed. This word is mapped in the easYgen to
the according database index.
CAN
AnalogManager
variable
Function
LDSS PL
ATS 1:
RPDO 1 “Word 2” is mapped to ID
3372
21.02 CAN1 RPDO1.2
Real power 1 [0.1kW]
If further ATS are in use:
CAN
AnalogManager
variable
Function
LDSS PL
ATS 2:
RPDO 2 “Word 2” is mapped to ID
3376
21.06 CAN1 RPDO2.2
Real power 2 [0.1kW]
ATS 3:
RPDO 3 “Word 2” is mapped to ID
3380
21.10 CAN1 RPDO3.2
Real power 3 [0.1kW]
ATS 4:
RPDO 4 “Word 2” is mapped to ID
3384
21.14 CAN1 RPDO4.2
Real power 4 [0.1kW]
ATS 5:
RPDO 5 “Word 2” is mapped to ID
3388
21.18 CAN1 RPDO5.2
Real power 5 [0.1kW]
6.3.15.3.3 Internally provided analog variables
These values can be assigned to the analog
variables of the Customer screens for
visualization.
10.73 Average load 1 [kW]
5 min average of “21.02 CAN1 RPDO1.2 “
10.74 Average load 2 [kW]
5 min average of “21.06 CAN1 RPDO2.2 “
10.75 Average load 3 [kW]
5 min average of “21.10 CAN1 RPDO3.2 “
10.76 Average load 4 [kW]
5 min average of “21.14 CAN1 RPDO4.2 “
10.77 Average load 5 [kW]
5 min average of “21.18 CAN1 RPDO5.2 “
10.78 Average load sum [kW]
If LDSS PL external is active, 10.78 is the load value
which is passed to the LDSS. It is the sum of all
averages (10.73 – 10.77) which have “Mains not
okay” and “GGB not closed”. In internal mode it is
the value of the 5 min. average of the AM
“Consumer load”.
761
easYgen-3000XT Series
B37574
6 Application Field
6.3.15.3.3 Internally provided analog variables
Released