◦ e. Bit 16 ATS start signal
◦
• “Word 2” with the mains power [0.1 kW resolution] signed.
•
These two words are mapped inside the easYgen to according database identifiers.
Binary flags from ATS (Word 1)
The word with the binary flags is filled up on the last 4 bits. This word is mapped in the
easYgen to the according database index. (According to the ATS number)
CAN
LogicsManager
Command Variable
Bit
ID
Function
LDSS PL
ID
De‐
script‐
ion
Field
ATS1:
RPDO 1
“Word 1”
is
mapped
to ID
3371
32.13 CAN1 RPDO1.1.13
13
11509
GGB closed
11573
32.14 CAN1 RPDO1.1.14
14
11510
MCB closed
11574
32.15 CAN1 RPDO1.1.15
15
11511
Mains OK
11575
32.16 CAN1 RPDO1.1.16
16
11512
ATS Start signal
11576
CAN
LogicsManager
Command Variable
Bit
ID
Function
LDSS PL
ID
De‐
script‐
ion
Field
ATS2:
RPDO 2
“Word 1”
is
mapped
to ID
3375
33.13 CAN1 RPDO2.1.13
13
11513
GGB closed
11577
33.14 CAN1 RPDO2.1.14
14
11514
MCB closed
11578
33.15 CAN1 RPDO2.1.15
15
11515
Mains OK
11579
33.16 CAN1 RPDO2.1.16
16
11516
ATS Start signal
11580
ATS3:
RPDO 3
“Word 1”
is
mapped
to ID
3379
34.13 CAN1 RPDO3.1.13
13
11517
GGB closed
1577
34.14 CAN1 RPDO3.1.14
14
11518
MCB closed
11578
34.15 CAN1 RPDO3.1.15
15
11519
Mains OK
11583
34.16 CAN1 RPDO3.1.16
16
11520
ATS Start signal
11584
ATS4:
RPDO 4
“Word 1”
is
mapped
to ID
3383
35.13 CAN1 RPDO4.1.13
13
11521
GGB closed
11585
35.14 CAN1 RPDO4.1.14
14
11522
MCB closed
11586
35.15 CAN1 RPDO4.1.15
15
11523
Mains OK
11587
35.16 CAN1 RPDO4.1.16
16
11524
ATS Start signal
11588
ATS5:
RPDO 5
“Word 1”
is
mapped
to ID
3387
36.13 CAN1 RPDO5.1.13
13
11525
GGB closed
11589
36.14 CAN1 RPDO5.1.14
14
11526
MCB closed
11590
36.15 CAN1 RPDO5.1.15
15
11527
Mains OK
11591
36.16 CAN1 RPDO5.1.16
16
11528
ATS Start signal
11592
Table 106: If further ATS are in use:
760
easYgen-3000XT Series
B37574
6 Application Field
6.3.15.3.2 LDSS PL CANopen Handling
Released