ID
Parameter
CL
Setting range
[Default]
Description
to the rules for phase-phase
systems.
Monitoring refers to the following
voltages:
• VL1N, VL12
•
1Ph 3W
Measurement is performed Line-
Neutral (WYE connected system)
and Line-Line (Delta connected
system).
The protection depends on the
setting of parameter
Measurement, display, and
protection are adjusted according
to the rules for single-phase
systems.
Monitoring refers to the following
voltages:
•
configured to "Phase-phase")
• VL1N, VL3N (parameter
•
configured to "Phase-
neutral")
• VL1N, VL3N (parameter
•
configured to "All")
Notes
If this parameter is configured to
1Ph 3W, the generator and mains
rated voltages (parameters
) must be
entered as Line-Line (Delta) and
the busbar 1 rated voltage
(parameter
entered as Line-Neutral (WYE).
1852
Mains current
measuring
2
[Phase L1]
Phase L2
Phase L3
Phase L{1/2/3} Measurement is
performed for the selected phase
only. The measurement and
display refer to the selected
phase.
The configured phase CT must be
connected to perform current
measurement.
Notes
For information on measuring
principles refer to
This parameter is only effective if
mains voltage measuring
(parameter
configured to "3Ph 4W" or "3Ph
3W".
595
easYgen-3000XT Series
B37574
4 Configuration
4.6.4 Mains
Released