External Breaker
Handling
Synchronizat‐
ion Mode
Dead Bus
Closure
Condition for the closure acceptance
GCB Synchronization
Off
-
• The start request in automatic is
•
active
• The generator is in operating range
•
• The engine start procedure is expired
•
GCB Dead bus closure
-
Off
MCB Synchronization
Off
-
The mains is in operating range
GCB Dead bus closure
-
Off
4.4.3.1
Good to know: Actions with Breakers
4.4.3.1.1
Dead Bus Closing GCB
The following applies to application modes
A03
and
A04
.
The unit closes the GCB without synchronization, if the following conditions are met. The
display indicates "GCB dead bus close".
Automatic operation
• The operating mode AUTOMATIC has been selected
•
• No class C alarm or higher is present
•
• The engine is running
•
• The engine delayed monitoring (parameter
) as well as the generator
•
) have been expired or the LogicsManager function
"Undelay close GCB" (parameter
• The generator voltage and frequency are within the configured operating range (
•
“4.5.1.1 Generator Operating Ranges: Voltage / Frequency / Busbar”
)
• The MCB has been opened for at least the time configured in "Transfer time
•
(Mode
A04
with open transition mode only)
• The function "Start without load" (parameter
) has been disabled through
•
the LogicsManager
• Only in critical mode: the parameter "Close GCB in override" (parameter
)
•
is configured to "Yes"
• The busbar voltage is below the dead bus detection limit (parameter
)
•
• There is no other GCB closed in the same segment
•
• There is no other device with a smaller device ID willing to close its GCB too (Dead
•
busbar closure negotiation)
Manual operation
• The operating mode MANUAL has been selected.
•
264
easYgen-3000XT Series
B37574
4 Configuration
4.4.3.1 Good to know: Actions with Breakers
Released