4.5.1
Configure Generator Monitoring
4.5.1.1
Generator Operating Ranges: Voltage / Frequency / Busbar
The operating voltage/frequency/busbar parameters are used to check if the values are
in range when performing a dead bus closure and synchronization of the generator.
Busbar 1 must be within this ranges to synchronize the generator to the busbar.
It is recommended to configure the operating limits within the monitoring limits.
ID
Parameter
CL
Setting range
[Default]
Description
5800
Upper voltage limit
(Generator maximum
operating voltage limit)
2
100 to 150%
[110%]
(Hysteresis: 1%)
The maximum permissible
positive deviation of the generator
voltage from the generator rated
voltage (parameter
) is
configured here.
This value may be used as a
voltage limit switch. The
conditional state of this switch
may be used as a command
variable for the LogicsManager
(02.03).
5801
Lower voltage limit
(Generator minimum
operating voltage limit)
2
50 to 100%
[90%]
(Hysteresis: 1%)
The maximum permissible
negative deviation of the
generator voltage from the
generator rated voltage
(parameter
configured here.
This value may be used as a
voltage limit switch. The
conditional state of this switch
may be used as a command
variable for the LogicsManager
(02.03).
5802
Upper frequency limit
(Generator maximum
operating frequency
limit)
2
100.0 to 150.0%
[105.0%]
(Hysteresis: 0.05%)
The maximum permissible
positive deviation of the generator
frequency from the rated system
frequency (parameter
is configured here.
This value may be used as a
frequency limit switch. The
conditional state of this switch
may be used as a command
variable for the LogicsManager
(02.04).
5803
Lower frequency limit
(Generator minimum
operating frequency
limit)
2
50.0 to 100.0%
[95.0%]
(Hysteresis: 0.05%)
The maximum permissible
negative deviation of the
generator frequency from the
rated system frequency
(parameter
configured here.
This value may be used as a
frequency limit switch. The
conditional state of this switch
may be used as a command
420
easYgen-3000XT Series
B37574
4 Configuration
4.5.1 Configure Generator Monitoring
Released