ID
Parameter
CL
Setting range
[Default]
Description
configured parameters to factory
default values is not enabled.
1701
Set factory default
values
4
Yes
All parameters, with the exception
of customer defined passwords,
will be restored to factory default
values. If the default setting is
initiated the alarm LED starts
twinkling with a higher rate (ca. 5
Hz).
Notes
The device is power cycled and
rebooting after approx. 20
seconds!
In case of ToolKit connected via
USB service port: USB connection
will be lost!
[No]
All parameters will remain as
currently configured.
Notes
This parameter is only displayed,
if factory default settings
(parameter
) is set to
"Yes".
1896
Parameter update
rate
4
3 - 7200 s
[3 s]
This parameter defines the time
for cyclical saving of changed
parameters in the non voluntary
memory. (Only accessible in
ToolKit.)
Notes
To ensure that parameter changes
are saved, wait at least this time
after parameter changes before
removing the power supply or
reboot.
Since memories only allow a
limited number of write cycles
(about 100000), set this value to a
longer time if, for example, you
write parameters cyclically via a
PLC. Otherwise, the lifetime of
the memory is shortened.
4.3.5.1
Reboot Function
The reboot of the device can be initiated by operating a Yes/No switch in ToolKit. This is
beneficial because some parameters, like
• 1893 Set device name,
•
• 3184 Modbus protocol number,
•
• 15320 Select external terminals and
•
• 15102 Device type
•
196
easYgen-3000XT Series
B37574
4 Configuration
4.3.5.1 Reboot Function
Released