HMI Text
Note
02.04 Gen. frequency ok
TRUE as long as the generator frequency is within the
operating range.
02.05 Gen. volt./freq. ok
TRUE as long as the generator voltage and frequency
are within the operating ranges (02.03. and 02.04 are
TRUE).
02.06 Busbar 1 voltage ok
TRUE as long as the busbar 1 voltage is within the
generator voltage operating range.
02.07 Busbar 1 freq. ok
TRUE as long as the busbar 1 frequency is within the
generator frequency operating range.
02.08 Busb1 volt./freq. ok
TRUE as long as the busbar 1 voltage and frequency
are within the generator operating ranges
(02.06. and 02.07 are TRUE).
02.09 Mains voltage ok
TRUE as long as the mains voltage is within the operating range.
This command variable is derived from the easYgen
mains measuremend, not from the LS5!
02.10 Mains frequency ok
TRUE as long as the mains frequency is within the operating range.
This command variable is derived from the easYgen
mains measuremend, not from the LS5!
02.11 Mains volt./freq. ok
TRUE as long as the mains voltage and frequency are within the operating ranges
(02.09. and 02.10 are
TRUE).
This command variable is derived from the easYgen
mains measuremend, not from the LS5!
02.12 Gen. rotation CCW
TRUE as long as the respective rotation field is
detected in case of a three-phase voltage measurement
at the respective measuring location.
02.13 Gen. rotation CW
TRUE as long as the respective rotation field is
detected in case of a three-phase voltage measurement
at the respective measuring location.
02.14 Mains rotation CCW
TRUE as long as the respective rotation field is
detected in case of a three-phase voltage measurement
at the respective measuring location.
These command variables are derived from the
easYgen mains measuremend, not from the LS5!
02.15 Mains rotation CW
TRUE as long as the respective rotation field is
1085