Fig. 212:
Application mode A01 (schematic)
The easYgen requires the feedback reply from GCB and MCB in this application mode.
These replies are used to define, whether the easYgen controls frequency, shares the
load with other gensets or performs active load control.
The following feedback signals are used in this application mode and fixed to the
respective discrete inputs:
• DI 7 "Reply MCB" (mains parallel)
•
• DI 8 "Reply GCB" (normally closed (break) contact)
•
If the easYgen is intended to be operated in parallel with the mains, the mains voltage
measuring inputs must be connected.
If an external mains decoupling is performed, jumpers between busbar and mains
voltage measuring inputs may be installed.
Engine operation in AUTOMATIC (basic function)
Engine starts, if
• The LogicsManager "86.09 LM: Start req.in AUTO" is fulfilled (TRUE) AND
•
• A shut down alarm is not present AND
•
681
easYgen-3000XT Series
B37574
6 Application Field
6.1.1 Application mode A01 (None)