Reactive power load sharing mismatch
ID
Parameter
CL
Setting range
[Default]
Description
5106
Monitoring
2
On
Load share monitoring is carried
out according to the following
parameters.
[Off]
Monitoring is disabled.
4842
Limit
2
1.0 to 100.0%
[30.0%]
The percentage value that is to be
monitored for the threshold limit is
defined here.
If this value is reached or
exceeded for at least the delay
time without interruption, the
action specified by the alarm class
is initiated.
Notes
This value is rated to the absolute
difference between generator
rated reactive power
(parameter
percent average reactive power of
the other devices. The generator
rated reactive power is modified
by the derating factor if derating
is activated.
5110
Delay
2
1.0 to 999.9 s
[10.0 s]
If the monitored generator power
value exceeds the threshold value
for the delay time configured
here, an alarm will be issued.
Notes
If the monitored generator power
falls below the threshold (minus
the hysteresis) before the delay
expires the time will be reset.
5107
Alarm class
2
Class A, Class B, Class C, Class D,
Class E, Class F , Control
[Class B]
Each limit may be assigned an
independent alarm class that
specifies what action should be
taken when the limit is surpassed.
Notes
For additional information refer to
5108
Self acknowledge
2
Yes
The control unit automatically
clears the alarm if the fault
condition is no longer detected.
[No]
The control unit does not
automatically reset the alarm
when the fault condition is no
longer detected.
The alarm must be acknowledged
and reset by manually pressing
the appropriate buttons or by
activating the LogicsManager
output "External
acknowledgment" (via a discrete
input or via an interface).
451
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.5 Load sharing
Released