HMI (Local Keylock). And finally it will be desired to switch off the remote panel
completely.
To maintain the different operating modes in the remote panel the easYgen has to
determine with LogicsManagers in which operation mode the Remote Panel RP-3000XT
shall run. If no LogicsManager is true, full mode with password suppression is active.
Following operation modes are defined (in order of the LogicsManager priority):
• RP-3000XT Full mode with password suppression (no LM true)
•
• RP-3000XT Full mode
•
• RP-3000XT Annunciator mode
•
• RP-3000XT Off mode (highest priority)
•
4.3.6.3
RP-3000XT in Full Mode with Password suppression
Fig. 135:
Remote Panel with display (plastic housing) variant of easYgen-XT
The RP-3000XT represents full the easYgen-3000XT (with Password suppression)
• All Operating Mode buttons are indicated and active
•
• The MAN Start Stop buttons are indicated and active
•
• The Acknowledge button is indicated and active
•
• The Alarm Symbol is indicated and active
•
• The “Home” button is indicated and active
•
• The Configuration capability is activated
•
• No suppress of any screen
•
• Password Screen is suppressed in the RP, if operated by easYgen-3000XT
•
• Password entry field of the Password Screen in the easYgen is suppressed, if
•
operated by RP-3000XT
The password suppressed Full Mode becomes active, if there is no mode selected via
LogicsManager.
If "Password display" entry field is operated in the RP-3000XT:
• "Password display" entry field in the easYgen is suppressed
•