ID
Parameter
CL
Setting range
[Default]
Description
[30%]
load-dependent start/stop function
will stop a genset.
If only a few gensets are operating
in a multi-genset application, the
MOP Dynamic (parameter
) will also be considered
when stopping a genset.
Notes
This parameter is only effective if
start stop mode (parameter
) is configured to "Generator
load".
The maximum generator load
must be configured higher then
the minimum generator load for
proper operation.
5758
MOP Dynamic
2
The dynamic determines when to
start or stop the next genset and
shows the following behavior:
Starting genset
The Dynamic is only considered
for the start sequence if "Fit size
of engines" is enabled (refer to
parameter
The control requests a certain
amount of additional load
depending on the dynamic. It may
start two or more gensets to
supply the required load.
Stopping genset
The dynamic determines how
soon a genset will be stopped. It
prevents continuous start and
stop if only a few gensets are in
operation.
In this case, the remaining
gensets would not reach the
maximum limit if one genset stops
(if, for example, two gensets with
100 kW rated load, a minimum
load of 40 % and a maximum load
of 70 % are operated, the second
genset will be shut down if both
reach 40 kW and the remaining
engine would operate with 80 kW
and request the next engine and
so on).
The more gensets are running, the
less the influence of this
parameter. Also refer to the
following example.
[Low]
Starting genset
A larger genset is requested and it
will take longer until the next
change is required. The engines
are operated with more reserve
412
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.5 Mains Parallel Operation
Released