ID
Parameter
CL
Setting range
[Default]
Description
5109
Enabled
2
[Always]
Monitoring for this fault condition
is continuously enabled.
87.70 LM:Eng.mon
Monitoring for fault conditions is
not performed until engine
monitoring is enabled. This is
determined through the
LogicsManager equation "Release
engine monitoring".
For xx = 1 to 32:
96.{xx}
LM: Flag{xx}
The monitoring is executed, if the
LogicsManager "Flag {xx}" is
TRUE.
Example:
96.01 LM: Flag 1, 96.02 LM: Flag
2, ..., 96.32 LM: Flag 32
4.5.1.5.6
Engine/Generator Active Power Mismatch
General notes
If enabled, this monitoring function becomes only active if generator power control is
enabled (refer to
). If the measured generator power deviates
from the power setpoint by a value exceeding the limit configured in parameter
for a time exceeding the delay configured in parameter
, an alarm will be
issued.
If this protective function is triggered, the display indicates "Gen act.pwr mismatch" and
the logical command variable "06.29" will be enabled.
ID
Parameter
CL
Setting range
[Default]
Description
2920
Monitoring
2
[On]
Monitoring of the generator active
power mismatch is carried out
according to the following
parameters.
Off
Monitoring is disabled.
2925
Limit
2
1.0 to 30.0%
[5.0%]
If the difference between the
measured generator power and
the power setpoint exceeds this
value for at least the delay time
(parameter
interruption, the action specified
by the alarm class is initiated.
Notes
This value refers to the generator
rated active power (parameter
2923
Delay
2
3 to 9999 s
[30 s]
If the monitored active power
mismatch exceeds the threshold
value configured in
parameter
452
easYgen-3000XT Series
B37574
4 Configuration
4.5.1.5.6 Engine/Generator Active Power Mismatch
Released