ID
Parameter
CL
Setting range
[Default]
Description
This can be useful in applications
with remote control, where the
operator wants to acknowledge
alarms and restart the engine
without the need to change
operating mode in the easYgen.
Notes
If the shut down alarm disappears,
generator can start automatically!
[Yes]
Each shut down alarm (class C, D,
E, F) will change operating mode
to STOP.
Notes
LM
,
5775
IOP Delayed unload.
Alarm C,E
2
0 to 9999 s
[0 s]
This parameter gives a load
sharing participant the
opportunity to delay the unload if
an shutdown alarm of alarm class
C or E occurs. The time gained
gives another generator the
chance to participate in the load
sharing network.
The time configured here delays
the triggering of alarm class C and
E. A setting of 0 s deactivates this
function.
Notes
For additional information refer to
4.5.6.2
Free Configurable Alarms
General Notes
The easYgen-XT provides 16 freely configurable alarms.
Each alarm is configurable by:
• A LogicsManager equation
•
• Alarm text/description (configurable with ToolKit only)
•
• Delay time
•
• Alarm class
•
• Self acknowledgment
•
• Being enabled depending on Engine Monitoring LM 87.70 (selectable)
•
556
easYgen-3000XT Series
B37574
4 Configuration
4.5.6.2 Free Configurable Alarms
Released