Message text
ID
Meaning
Ignition
13213
Enable the ignition (Gas engine)
After the purging operation and before the fuel solenoids opened.
Preglow
13208
Preglow of the engine is active (Diesel engine)
The diesel engine is preheated prior to starting.
Turning
13212
Purging operation is active (Gas engine)
Before the fuel solenoid opens and the ignition of the gas engine is energized the
remaining fuel, that may be present in the combustion chamber, will be removed
by a purging operation. The starter turns the engine without enabling the ignition
for a specified time to complete the purging operation. After the purging process,
the ignition is energized.
Start w/o Load
13263
Start without load is active
A regular engine start is performed. The GCB operation is blocked to prevent a
change from mains to generator supply.
Emergency run
13211
Emergency power operation
After the control unit detects that a mains fault has occurred, the engine is started
after the emergency delay timer expires. The MCB is opened, the GCB is closed,
and the generator set assumes the load. If the generator set is already running,
operations continue until the emergency power operation conditions no longer
exist. If the mains return, the mains settling timer becomes active first.
Run-up Synchron.
13271
Run-up Synchronization
The run-up synchronization mode is active.
Derating active
13281
Derating active
As long as the derating function is activated, this text message is shown.
Inhibit cranking
13284
Inhibit cranking
The cranking is blocked.
Uprating active
13287
Uprating active
As long as the uprating function is activated, this text message is shown.
Gen excitation lim.
13288
Generator excitation limit is reached
During regulation kvar at the interchange point the maximum allowed excitation
current is reached.
P(V) derating
13309
P(V) derating is active
System update
14763
System update is active
The system update procedure is ongoing.
Keypad locked
14775
The keypad easYgen is locked
Loading generator
13258
The generator power will be increased to the setpoint
The generator power will be increased to the configured setpoint with a rate
defined by the power control setpoint ramp.
Unloading mains
13264
The mains power will be decreased
The real power setpoint is increased with the configured rate after synchronizing
the generator in interchange transition mode. After the mains have been
unloaded, the MCB will be opened.