Start engine
The engine is started via a remote start signal.
Prerequisites:
• The AUTOMATIC operating mode is enabled.
•
• The start request is enabled by the LogicsManager Start req. in AUTO.
•
• No shut down alarm is present. (for explanation of the alarm classes refer to
•
).
• The engine is ready for operation.
•
• The GCB is open.
•
Auto mains failure operation (AMF)
Auto mains failure operation is only available in application mode
A04
.
If the AUTOMATIC operating mode is enabled and the mains fail, the engine and the
power circuit breakers will be operated according to the current application mode.
Prerequisites:
• The AUTOMATIC operating mode is enabled.
•
• The parameter "Emergency power" is configured to "On".
•
• The configured mains failure limits are reached.
•
• The configured delay times have expired.
•
• No shut down alarm is present. (for explanation of the alarm classes refer to
•
).
• The engine is ready for operation.
•
5.2.4
Operating Mode TEST
General usage
The operating mode (»TEST«) usually is a temporary operating mode. The idea is to test
the genset.
TEST operating mode always starts the engine, when changing into this mode
independent on an AUTOMATIC start order. Additionally the TEST operating mode
supports the emergency and critical run as well (if a mains failure occurs during the test
run). The operating mode TEST supports different sub modes so the operator can choose
if the breakers shall be closed during test run or whether the operating mode is changed
after the test run.