Message text
ID
Meaning
The frequency / voltage regulation for synchronization is enabled. The according
breaker close pulse is disabled.
Synch. OFF
13267
Synchronization mode OFF
The frequency / voltage regulation for synchronization is disabled. The close pulse
is disabled.
Inh.dead bus closure
13311
Inhibit dead bus closure
The dead busbar closure is inhibited.
GCB closure disabled
13247
GCB shall be closed but is not enabled by LM
GC System update
14776
GC System update is active
9.5.2
Event History
General notes
The event history is a 1000 entry FIFO (First In/First Out) memory for logging alarm events
and operation states of the unit. As new event messages are entered into the history, the
oldest messages are deleted once 1000 events have occurred.
For additional information refer to
.
Resetting event history
Make sure to have set the appropriate code level to reset the event history.
If you have not entered the correct password for the required code level, the parameters
for resetting the event history are not available (for additional information refer to
“4.3.4.1 Password System - Parameter Overview”
Three ways to reset Event History
• ToolKit: Click the »Clear all « button at [STATUS MENU / Diagnostic / Event History].
•
(Read Event History at the same page)
• HMI/display: Go to [Parameter / Configure system management / Factory default
•
settings] and select »Yes«, then »Clear eventlog« appears. Select »Yes« for »Clear
event log«
(To read Event History go to: [Next Page / Diagnostic / Event History])
• Parameter/remote:Set parameter
»Clear eventlog« ) to "TRUE" (1)
•
• The complete event history is now being cleared
•
9.5.3
Event Message
Message text
ID
Meaning
AUTO mode
14353
The unit is switched to AUTO mode
1176
easYgen-3000XT Series
B37574
9 Appendix
9.5.2 Event History
Released