ID
Parameter
CL
Setting range
[Default]
Description
configured here, the higher the
priority.
This priority may be overridden by
the LDSS Priority parameters
(parameters
12926
LDSS Priority 2
2
Determined by LogicsManager
86.90
[(0 & 1) & 1]
= 111919
Once the conditions of the
LogicsManager have been fulfilled,
the load-dependent start/stop
priority will be set to 2 (the
highest priority is valid).
Notes
For information on the
LogicsManager and its default
settings see
.
12925
LDSS Priority 3
2
Determined by LogicsManager
86.91
[(0 & 1) & 1]
= 11920
Once the conditions of the
LogicsManager have been fulfilled,
the load-dependent start/stop
priority will be set to 3 (the
highest priority is valid).
Notes
For information on the
LogicsManager and its default
settings see
.
12924
LDSS Priority 4
2
Determined by LogicsManager
86.92
[(0 & 1) & 1]
= 11921
Once the conditions of the
LogicsManager have been fulfilled,
the load-dependent start/stop
priority will be set to 4 (the
highest priority is valid).
Notes
For information on the
LogicsManager and its default
settings see
.
5754
Fit size of engine
2
This parameter defines whether
the start/stop priority order (
“4.4.5.5.3 Generator Selection”
considers the size of the engine
(generator rated power) or not. In
case of different sized gensets,
the control can start a genset
combination which results in
optimum efficiency.
The fuel efficiency may be
optimized when this parameter is
enabled. This parameter may be
disabled if all generators have the
same size.
Notes
The algorithm prefers one large
engine instead of multiple small
399
easYgen-3000XT Series
B37574
4 Configuration
4.4.5.5.3 Generator Selection
Released